The RISE Duct Seal is a multi-cable and pipe transit sealing system, delivering proven technology and lifetime performance. It provides an effective and simple solution to all fireproof, gas tight and water tight duct sealing requirements. It consists of only two components: RISE rubber insert sleeves, used to guarantee cable separation and as a backing for the sealant layer, and FIWA sealant, a high quality silicone based, fire stopping, water repellent sealant which consequently makes the system quick and easy to install.
View more photos
Gas tight and water tight
The elasticity and high bonding strength of sealant offers a flexible seal which resists movement, shock and vibration, as well as high pressure. The RISE rubber insert sleeves are applied to guarantee cable separation and as a backing for the application of the sealant. For gas tight and water tight applications, our standard 60mm RISE sleeve is sufficient.
Fire, gas and water tight
Using our fire resistant RISE insert sleeves at a length of 160mm and applying sealant to both faces of the opening, will provide a fire stopping seal. When exposed to heat or flame, the advanced rubbers used within the system will resist heat and flame, assuring total conduit sealing protection against fire, heat, toxic and corrosive gases.
Flexible and versatile
The RISE System can be used in vertical as well as horizontal ducts. The split insert sleeves cling to the cables without sliding down and falling out of the penetration, bundled multi sleeves are available for any openings with lots of free space.The high adhesion and viscosity of the sealant means it will not run or drip when applied overhead. Using the newly developed Aquastop or a drain during installation allows the RISE system to be used in sealing ducts when there is running water.
Adding/removing cables
Installing additional cables is very straightforward. It is a simple matter of coring into the soft rubber layer of the sealant to a depth of 20mm and passing the additional cables through the opening created. The sealant is then applied around the new cable to re-seal. There is no need to disassemble the whole transit.